33
2F (L) Filter Bit 7 6 5 4 3 2 1 0
0 0 0 0 Auto Filter
0 0 0 1 Batch (16 samples) filter
Time constant 60 Hz 50 Hz
0 0 1 0 Moving average 0.07 s 0.085 s
0 0 1 1 Moving average 0.14 0.17
0 1 0 0 Moving average 0.28 0.34
0 1 0 1 Moving average 0.57 0.68
0 1 1 0 Moving average 1.13 1.36
0 1 1 1 Moving average 2.27 2.72
1 0 0 0 Moving average 4.53 5.44
1 0 0 1 Moving average 9.06 10.88
1 0 1 0 Unfiltered
0 Low adaptive threshold
1 High adaptive threshold
0 Display batch
1 Display filtered signal
0 Take peak of unfiltered signal
1 Take peak of filtered signal
0 Alarm from unfiltered signal
1 Alarm from filtered signal
2D (L) Setup Bit 7 6 5 4 3 2 1 0 EXT IN 1 EXT IN 2 BOTH
0 0 0 0 Mtr Reset Mtr Hold Mtr Reset
0 0 0 1 Fct Reset Rd Pk/Vl Mtr Reset
0 0 1 0 Mtr Hold Rd Pk/Vl Fct Reset
0 0 1 1 Mtr Hold Tare Mtr Reset
0 1 0 0 Rd Pk/Vl Tare Fct Reset
0 1 0 1 Tare Mtr Reset Mtr Reset
0 1 1 0 DP2 DP3 DP4
0 1 1 1 DP3 DP4 DP5
1 0 0 0 Fct Reset Disp Blank Mtr Reset
1 0 0 1 Mtr Hold Disp Blank Mtr Reset
1 0 1 0 Rd Pk/Vl Disp Blank Fct Reset
1 0 1 1 Tare Disp Blank Mtr Reset
1 1 0 0 Rd Valley Read Peak Fct Reset
1 1 0 1 Tare Tare Reset Mtr Reset
0 0 Scale using Scale & Offset method
0 1 Scale using Coordinates of 2 Points method
1 1 Scale using Reading Coordinates of 2 Points
0 60 Hz power
1 50 Hz power